![](https://ibcon.com/main/wp-content/uploads/2023/07/SIMATICIoT2000_IO_01.jpg)
![](https://ibcon.com/main/wp-content/uploads/2024/12/6ES7647-0KA01-0AA2.jpg)
SIMATIC IoT2000 input/output module
IO shield for SIMATIC IOT2000 Industrial IoT Gateways
The SIMATIC IOT2000 IO shield allows for direct connection of non-time-critical sensor data to the SIMATIC IOT2000 via digital and analog IOs.
Specifications
Article number | 6ES7647-0KA01-0AA2 SIMATIC IoT2000 input/output module | |
---|---|---|
General information | ||
Product type designation | IOT2000 | |
Installation type/mounting | ||
Mounting | On Arduino interface | |
Design | Plug-in card | |
Supply voltage | ||
Type of supply voltage | 24 V DC | |
Digital inputs | ||
Number of digital inputs | 5 | |
Input voltage | ||
● Type of input voltage | DC | |
● for signal “0” | < 5 V DC | |
● for signal “1” | > 12 V DC | |
Input current | ||
● for signal “0”, max. (permissible quiescent current) | 0.9 mA | |
● for signal “1”, typ. | 2.1 mA | |
Input delay (for rated value of input voltage) for standard inputs | ||
— at “0” to “1”, max. | 1.5 ms | |
— at “1” to “0”, max. | 1.5 ms | |
Digital outputs | ||
Type of digital output | transistor | |
Number of digital outputs | 2 | |
Short-circuit protection | Yes | |
Output voltage | ||
● Type of output voltage | DC | |
● permissible voltage at output, min. | 0 V | |
● permissible voltage at output, max. | 28.8 V | |
Output current | ||
● for signal “1” rated value | 0.3 A | |
Parallel switching of two outputs | ||
● for uprating | No | |
Switching frequency | ||
● with resistive load, max. | 10 Hz | |
● with inductive load, max. | 0.5 Hz | |
Analog inputs | ||
Number of analog inputs | 2 | |
Input ranges | ||
● Voltage | Yes; 0 to 10V | |
● Current | Yes; 0 to 20 mA | |
● Thermocouple | No | |
● Resistance thermometer | No | |
● Resistance | No | |
Input ranges (rated values), voltages | ||
● 0 to +10 V | Yes | |
Input ranges (rated values), currents | ||
● 0 to 20 mA | Yes | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 9 bit | |
Integrated Functions | ||
Monitoring functions | ||
● Temperature monitoring | No | |
● Watchdog | No | |
● Status LEDs | No | |
● Fan | No | |
EMC | ||
Interference immunity against discharge of static electricity | ||
● Interference immunity against discharge of static electricity | ±4 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC 61000-4-2 | |
Interference immunity against high-frequency electromagnetic fields | ||
● Interference immunity against high frequency radiation | 10 V/m for 80 – 1 000 MHz, 80% AM acc. to IEC 61000-4-3; 3 V/m for 1.4 – 2 GHz, 80% AM acc. to IEC 61000-4-3; 1 V/m for 2 – 2.7 GHz, 80% AM acc. to IEC 61000-4-3; 10 V for 150 kHz – 80 MHz, 80% AM acc. to IEC 61000-4-6 | |
Interference immunity to cable-borne interference | ||
● Interference immunity on supply cables | ±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge symmetric; ±2 kV acc. to IEC 61000-4-5, surge asymmetric | |
● Interference immunity on signal cables >30m | ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m | |
● Interference immunity on signal cables < 30m | ±2 kV in accordance with IEC 61000-4-4, burst, length > 30 m | |
Interference immunity against voltage surge | ||
● asymmetric interference | ±2 kV acc. to IEC 61000-4-5, surge asymmetric | |
● symmetric interference | ±1 kV acc. to IEC 61000-4-5, surge symmetric | |
Interference immunity to magnetic fields | ||
● Interference immunity to magnetic fields at 50 Hz | 100 A/m; to IEC 61000-4-8 | |
Emission of conducted and non-conducted interference | ||
● Interference emission via line/AC current cables | EN 61000-6-4:2007 +A1:2011 | |
Degree and class of protection | ||
IP (at the front) | n.a. | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes | |
cULus | Yes | |
KC approval | Yes; For use inside SIMATIC IoT2040 | |
EMC | CE, EN 61000-6-4:2007 +A1:2011, EN 61000-6-2:2005, EN 61000-6-3:2007 +A1:2011, EN 61000-6-1:2007 | |
Ambient conditions | ||
Ambient temperature during operation | ||
● Ambient temperature during operation | 0 °C to 50 °C | |
Relative humidity | ||
● Relative humidity | Tested according to IEC 60068-2-78, IEC 60068-2-30: Operation: 5 % to 85 % at 30 °C (no condensation), storage / transport: 5 % to 95 % at 25 / 55 °C (no condensation) | |
Vibrations | ||
● Vibration resistance during operation acc. to IEC 60068-2-6 | Tested according to IEC 60068-2-6: 5 Hz to 9 Hz: 3.5 mm; 9 Hz to 200 Hz: 9.8 m/s² | |
Shock testing | ||
● Shock load during operation | Tested according to IEC 60068-2-27: 150 m/s², 11 ms | |
Operating systems | ||
without operating system | Yes | |
Dimensions | ||
Width | 75 mm | |
Height | 57 mm | |
Depth | 32 mm |