LOGO!Power

LOGO!Power 24 V DC

Overview

Thanks to its stepped profile design, the LOGO!Power product line is ideally suited for installation in small distribution boards. The stabilized power supplies with wide-range input are available with an output voltage of 24 V in four performance classes. The 24 V versions are ideal for supplying LOGO! PLCs with the corresponding voltage input.

To further increase the 24 V availability, the LOGO!Power power supply units can be combined with DC UPSredundancy and selectivity modules.


Product highlights

  • 1-phase, 24 V DC/ 0.6 A, 1.3 A, 2.5 A and 4.0 A
  • Input voltage 100 … 240 V AC (85 … 264 V), 110 … 300 V DC
  • Narrow unit with width of 18 mm, 36 mm, 54 mm or 72 mm and overall depth of 53 mm in LOGO! design
  • Up to 90% efficiency
  • Integrated current monitor: Actual output current measurement directly at the power supply unit (for devices at least 36 mm wide)
  • cULus, cURus, NEC class 2, ABS, BV, DNV GL, LRS certifications

Specifications

Article number6EP3330-6SB00-0AY06EP3331-6SB00-0AY06EP3332-6SB00-0AY06EP3333-6SB00-0AY0
ProductLOGO!PowerLOGO!PowerLOGO!PowerLOGO!Power
Power supply, type24 V/0.6 A24 V/1.3 A24 V/2.5 A24 V/4 A
Input
type of the power supply network1-phase AC or DC1-phase AC or DC1-phase AC or DC1-phase AC or DC
supply voltage at AC
● minimum rated value100 V100 V100 V100 V
● maximum rated value240 V240 V240 V240 V
● initial value85 V85 V85 V85 V
● full-scale value264 V264 V264 V264 V
input voltage    
● at DC110 … 300 V110 … 300 V110 … 300 V110 … 300 V
design of input wide range inputYesYesYesYes
overvoltage overload capability300 V AC for 1 s300 V AC for 1 s300 V AC for 1 s300 V AC for 1 s
operating condition of the mains bufferingat Vin = 187 Vat Vin = 187 Vat Vin = 187 Vat Vin = 187 V
buffering time for rated value of the output current in the event of power failure minimum40 ms40 ms40 ms40 ms
operating condition of the mains buffering line frequencyat Vin = 187 Vat Vin = 187 Vat Vin = 187 Vat Vin = 187 V
● 1 rated value50 Hz50 Hz50 Hz50 Hz
● 2 rated value60 Hz60 Hz60 Hz60 Hz
line frequency47 … 63 Hz47 … 63 Hz47 … 63 Hz47 … 63 Hz
input current
● at rated input voltage 120 V0.3 A0.7 A1.22 A1.95 A
● at rated input voltage 230 V0.2 A0.35 A0.66 A0.97 A
current limitation of inrush current at 25 °C maximum20 A25 A52 A31 A
I2t value maximum0.8 A²·s0.8 A²·s3 A²·s2.5 A²·s
fuse protection typeinternalinternalinternalinternal
● in the feederRecommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic CRecommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic CRecommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic CRecommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C
Output
voltage curve at outputControlled, isolated DC voltageControlled, isolated DC voltageControlled, isolated DC voltageControlled, isolated DC voltage
output voltage at DC rated value24 V24 V24 V24 V
output voltage    
● at output 1 at DC rated value24 V24 V24 V24 V
relative overall tolerance of the voltage3 %3 %3 %3 %
relative control precision of the output voltage    
● on slow fluctuation of input voltage0.1 %0.1 %0.1 %0.1 %
● on slow fluctuation of ohm loading0.1 %0.1 %0.1 %0.1 %
residual ripple    
● maximum200 mV200 mV200 mV200 mV
● typical30 mV30 mV30 mV30 mV
voltage peak    
● maximum300 mV300 mV300 mV300 mV
● typical50 mV50 mV50 mV50 mV
adjustable output voltage22.2 … 26.4 V22.2 … 26.4 V22.2 … 26.4 V
product function output voltage adjustableNoYesYesYes
type of output voltage settingvia potentiometervia potentiometervia potentiometer
display version for normal operationGreen LED for output voltage OKGreen LED for output voltage OKGreen LED for output voltage OKGreen LED for output voltage OK
behavior of the output voltage when switching onNo overshoot of Vout (soft start)No overshoot of Vout (soft start)No overshoot of Vout (soft start)No overshoot of Vout (soft start)
response delay maximum0.5 s0.5 s0.5 s0.5 s
voltage increase time of the output voltage    
● typical100 ms100 ms100 ms100 ms
output current    
● rated value0.6 A1.3 A2.5 A4 A
● rated range0 … 0.6 A; +55 … +70 °C: Derating 2%/K0 … 1.3 A; +55 … +70 °C: Derating 2%/K0 … 2.5 A; +55 … +70 °C: Derating 2%/K0 … 4 A; +55 … +70 °C: Derating 2%/K
supplied active power typical14.4 W31.2 W60 W96 W
product feature    
● bridging of equipmentNoYesYesYes
number of parallel-switched equipment resources for increasing the power222
Efficiency
efficiency in percent81 %86 %89.6 %89.1 %
power loss [W]    
● at rated output voltage for rated value of the output current typical3.4 W5.1 W7 W11.7 W
● during no-load operation maximum0.3 W0.3 W0.3 W0.3 W
Closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.2 %0.2 %0.2 %0.2 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical2 %1 %2 %2 %
setting time    
● load step 10 to 90% typical1 ms1 ms1 ms1 ms
● load step 90 to 10% typical1 ms1 ms1 ms1 ms
Protection and monitoring
design of the overvoltage protectionYes, according to EN 60950-1Yes, according to EN 60950-1Yes, according to EN 60950-1Yes, according to EN 60950-1
● typical0.8 A1.7 A3.2 A5 A
property of the output short-circuit proofYesYesYesYes
design of short-circuit protectionConstant current characteristicConstant current characteristicConstant current characteristicConstant current characteristic
enduring short circuit current RMS value    
● maximum0.8 A1.7 A3.2 A5 A
overcurrent overload capability in normal operationoverload capability 150% Iout rated typ. 200 msoverload capability 150% Iout rated typ. 200 msoverload capability 150% Iout rated typ. 200 msoverload capability 150% Iout rated typ. 200 ms
display version for overload and short circuit
measuring point for output current50 mV =^ 1.3 A50 mV =^ 2.5 A50 mV =^ 4 A
overcurrent overload capability when switching on150% Iout rated typ. 200 ms150% Iout rated typ. 200 ms150% Iout rated typ. 200 ms150% Iout rated typ. 200 ms
Safety
galvanic isolation between input and outputYesYesYesYes
galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection classClass II (without protective conductor)Class II (without protective conductor)Class II (without protective conductor)Class II (without protective conductor)
protection class IPIP20IP20IP20IP20
Approvals
certificate of suitability    
● CE markingYesYesYesYes
● UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● CSA approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310)Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● cCSAus, Class 1, Division 2NoNoNoNo
● ATEXNoNoNoNo
certificate of suitability    
● IECExNoNoNoNo
● NEC Class 2YesYesYesNo
● ULhazloc approvalNoNoNoNo
● FM registrationNoNoNoNo
type of certification CB-certificateYesYesYesYes
certificate of suitability    
● EAC approvalYesYesYesYes
certificate of suitability shipbuilding approvalYesYesYesYes
shipbuilding approvalABS, BV, DNV GL, LRSABS, BV, DNV GL, LRSABS, BV, DNV GL, LRSABS, BV, DNV GL, LRS
Marine classification association    
● American Bureau of Shipping Europe Ltd. (ABS)YesYesYesYes
● French marine classification society (BV)YesYesYesYes
● DNV GLYesYesYesYes
● Lloyds Register of Shipping (LRS)YesYesYesYes
● Nippon Kaiji Kyokai (NK)NoNoNoNo
EMC
standard    
● for emitted interferenceEN 55022 Class BEN 55022 Class BEN 55022 Class BEN 55022 Class B
● for mains harmonics limitationnot applicablenot applicablenot applicableEN 61000-3-2
● for interference immunityEN 61000-6-2EN 61000-6-2EN 61000-6-2EN 61000-6-2
environmental conditions
ambient temperature    
● during operation-25 … +70 °C; with natural convection-25 … +70 °C; with natural convection-25 … +70 °C; with natural convection-25 … +70 °C; with natural convection
● during transport-40 … +85 °C-40 … +85 °C-40 … +85 °C-40 … +85 °C
● during storage-40 … +85 °C-40 … +85 °C-40 … +85 °C-40 … +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 … 95% no condensationClimate class 3K3, 5 … 95% no condensationClimate class 3K3, 5 … 95% no condensationClimate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connectionscrew-type terminalsscrew-type terminalsscrew-type terminalsscrew-type terminals
● at inputL, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely strandedL, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely strandedL, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely strandedL, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely stranded
● at output+, -: 1 screw terminal each for 0.5 … 2.5 mm²+, -: 1 screw terminal each for 0.5 … 2.5 mm²+, -: 1 screw terminal each for 0.5 … 2.5 mm²+, -: 1 screw terminal each for 0.5 … 2.5 mm²
● for auxiliary contacts
width of the enclosure18 mm36 mm54 mm72 mm
height of the enclosure90 mm90 mm90 mm90 mm
depth of the enclosure53 mm53 mm53 mm53 mm
required spacing    
● top20 mm20 mm20 mm20 mm
● bottom20 mm20 mm20 mm20 mm
● left0 mm0 mm0 mm0 mm
● right0 mm0 mm0 mm0 mm
net weight0.07 kg0.12 kg0.2 kg0.29 kg
product feature of the enclosure housing can be lined upYesYesYesYes
fastening methodSnaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positionsSnaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positionsSnaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positionsSnaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positions
MTBF at 40 °C4 415 040 h3 094 996 h2 864 520 h2 391 480 h
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)